Product Information
Traffic Type: Commercial
Overall/Wear Layer Thickness: 1/8″ (3.2 mm)
Length x Width: 12″ x 12″ (30.5 cm x 30.5 cm)
Finish: Fast Start® (S-392 polish required before traffic)
Face Treatment: Traditional Smooth
Edge Treatment: Square Edges
Manufacturing Location: USA
Warranty
5 Year Commercial Limited Warranty
Product Structure

Applications
Reasons to Specify Static Control Flooring
- Dissipates static to increase safety and prevent damage to expensive equipment
- Provides a continuous static dissipative surface throughout the space – tile-to-tile connectivity
- Long life value with true through-pattern VCT
- Exclusive Fast Start Factory Finish makes initial maintenance quick and easy
- Made in USA with global and domestic content
Excelon SDT is a complete system. Each component enhances the total performance:
- Tile with integral static dissipative elements
- S-202 Static Dissipative Adhesive
- Copper grounding strips (included with S-202 adhesive)
- S-392 Static Dissipative Polish
Applications For ESD Flooring
- Computer training rooms
- Data warehousing
- Electronic testing labs
- Electronics Manufacturing
- Hyperbaric spaces in healthcare settings
Product Features
See the Excelon Static Dissipative Tile collection at ArmstrongFlooring.com
Excelon SDT static dissipative tile is a complete flooring solution designed to control static in most non-explosive manufacturing and working areas. The exclusive four-part system comprised of tile, adhesive, copper grounding strips, and polish, works together to dissipate electrostatic charges, protecting people and preventing damage to expensive equipment.
MATERIAL: A composition of polyvinyl chloride resin, binder, fillers, pigments, and antistatic additive.
PATTERNS AND COLORS: Colors and pattern are dispersed uniformly throughout the thickness of the material. Color pigments are insoluble in water and resistant to cleaning agents and light.
REFERENCE SPECIFICATIONS:
ASTM F 1066 Vinyl Composition Floor Tile, Class 2 – through pattern Meets requirements for size, thickness, squareness, indentation, impact, dimensional stability and resistance to chemicals.
ELECTRICAL PROPERTIES
- Installed as a system using the required adhesive, grounding strips and polish, SDT yields the following electrical properties:
- Resistance: ANSI / ESD-S7.1 and ASTM F-150
- Point to point and point to ground: 106 to 109 ohms
- Static Generation: ANSI / ESD STM 97.2 (flooring in combination with footwear and a person)
- at 40% R.H. with ESD shoes: <10 volts
- at 12% R.H. with ESD shoes: <10 volts
- Static Dissipation at 12% R.H.: Flooring in combination with a person wearing dissipative footware:
- 1000 to 100 volts: 0.2 seconds avg.
Testing
Per ASTM F 1066 | |||
---|---|---|---|
Performance | Test Method | Requirement | Performance vs. Requirement |
Thickness | ASTM F 386 | Nominal ± 0.005 in. | Meets |
Size | ASTM F 2055 | ± 0.016 in. per linear foot | Meets |
Squareness | ASTM F 2055 | 0.010 in. max | Meets |
Indentation – One Minute | ASTM F 1914 | ≥ 0.006 in. to ≤ 0.015 in. | Meets |
Indentation @ 115°F | ASTM F 1914 | < 0.032 in. | Meets |
Impact | ASTM F 1265 | No cracks beyond limit | Meets |
Deflection | ASTM F 1304 | 1.0 in. minimum | Meets |
Dimensional Stability | ASTM F 2199 | ≤ 0.024 in. per linear foot max. | Meets |
Chemical Resistance | ASTM F 925 | No more than slight change in surface dulling, attack or staining | Meets |
Resistance to Heat | ASTM F 1514 | ΔE not greater than 8.0 | Meets |
Additional Testing | |||
---|---|---|---|
Performance | Test Method | Requirement | Performance vs. Requirement |
Resistance* | ANSI / ESD STM 7.1 ASTM F-150 | Point to point and point to ground: 106 to 109 ohms | — |
Resistance in Combination with a Person* | ANSI / ESD STM 97.1 | at 12% R.H. w/ Dissipative footwear: 4.48 x 108 ohms (average) | — |
Static Generation* | ANSI / ESD STM 97.2 | at 12% R.H. with Dissipative footwear: 30 volts (average) | — |
Static Dissipation* | ETS Dissipation Method | at 12% R.H with Dissipative footwear 1000 to 100 volts: 0.2 seconds max. | — |
Static Load Limit | ASTM F 970 | ≤ 0.005 in. | 75 psi |
Fire Test Data – Flame Spread | ASTM E 648 | 0.45 w/cm2 or more Class I | Meets |
Fire Test Data – Smoke Evolution | ASTM E 662 | 450 or less | Meets |
Fire Test Data – Canada | CAN\ULC S102.2 | Use dependent | Flame Spread – 0 Smoke Developed – 30 |
ADA Standards for Accessible Design | Chapter 3 Section 302.1 | Floor surfaces shall be stable, firm and slip-resistant | Meets |
Static Coefficient of Friction** | ASTM D 2047/UL 410 | ≥ 0.5 | Meets |
Static Coefficient of Friction with S-392 Polish** | ASTM D 2047/UL 410 | ≥ 0.5 | Meets |
** Using the James Machine as described in ASTM D2047 and as directed in UL 410 for Floor Covering Materials (FCM) using a leather sensor under dry conditions. Other than Armstrong S-392 Static Dissipative Tile Polish, the application of floor sealers or finishes of any kind during or after installation will change the pedestrian walking surface and, as a result, the Static Coefficient of Friction (SCOF) value.
Recommended Applications
Recommended Applications Chart – Vinyl Composition Tile
Installation
Location: | All grade levels |
System: | SDT (Static Dissipative Tile) Installation System |
Fitting: | Tile cutter, straight scribe, hot knife |
Adhesives: | S-202 |
Installation Special Precautions and Recommendations:
- Refer to the SDT (Static Dissipative Tile) Installation System for complete installation recommendations.
- The SDT Installation System requires the use of copper grounding strips supplied with S-202 Adhesive.
- If electrical certification of an installation is required, do not perform any maintenance procedures until after that certification has been completed.
- Use only Armstrong S-392 Static Dissipative Tile Polish on SDT. Refer to the SDT maintenance Procedures for complete maintenance recommendations.
- Do not install SDT in areas subject to excessive surface water or frequent spills.
- Do not install over existing resilient flooring.
- Pattern and Shade/Lot Numbers should match.
Sustainability
LEED Credit Information – Commercial
Sustainable Design Information
FloorScore Certificates – Vinyl Composition Tile
Environmental Product Declaration (EPD) – Vinyl Composition Tile
SDS
Excelon Static Dissipative Tile MIS
Care and Maintenance
Maintenance Recommendations:
Maintenance Instructions for Static Dissipative Tile (SDT)
Maintenance Products:
Cleaner: Armstrong Flooring S-485
Polish: Armstrong Flooring S-392
Product Data Table
CARTON PROPERTIES | |
Pieces Per Carton | 45 |
Length | 12.4″ (31.5 cm) |
Width | 12.4″ (31.5 cm) |
Height | 6″ (15.2 cm) |
Coverage Per Carton | 45 sq ft (4.18 sq m) |
Carton Weight | 63 lbs (28.6 kg) |
PALLET PROPERTIES | |
Cartons Per Pallet | 24 |
Coverage Per Pallet | 1080 sq ft (100.32 sq m) |
Static Dissipative Tile Model Number | Color | Suffix |
51951 | Armor Gray | 031 |
51956 | Fossil Gray | 031 |
51950 | Marble Beige | 031 |
51955 (Disc 07/19) | Moss Green | 031 |
51953 | Pearl White | 031 |
51954 (Disc 07/19) | Sandstone Beige | 031 |
51957 | Ridge | 031 |
51958 | Ocean Air | 031 |
51959 | Coal | 031 |
51960 | Beach | 031 |
Static Dissipative Tile Model Number | Color | Suffix |